Test Report
Transkript
Test Report
CESI PUBBLICATO A8003390 (PAD - 1017314) Test Report A8003390 Approved Page 1/16 Client ELTAS Transformatör Sanayi Ve Ticaret Anonim Şirketi Izmir – TURKEY Test equipment Complete column of a three-phase 500 kVA dry-type power transformer Tests carried out Fire behaviour test F1 class Standards/Specifications IEC 60076-11, 2004 clause 28.3 to 28.8 Test date from February 5, 2008 to February 5, 2008 The test results relate only to the sample tested. Mod. RPRO v. 02 This document shall not be reproduced except in full without the written approval of CESI. No. of pages 16 Issue date February 6, 2008 Prepared Unit LABORATORIES – Roberto Mariani Verified Unit LABORATORIES – Franco Pizzi Approved Area COMPONENTS – Virginio Scarioni CESI Centro Elettrotecnico Sperimentale Italiano Giacinto Motta SpA No. of pages annexed Via R. Rubattino 54 20134 Milano - Italia Telefono +39 022125.1 Fax +39 0221255440 www.cesi.it Capitale sociale 8 550 000 Euro interamente versato Codice fiscale e numero iscrizione CCIAA 00793580150 Registro Imprese di Milano Sezione Ordinaria N. R.E.A. 429222 P.I. IT00793580150 CESI Test Report Test witnessed by Mr. Ahmet Gure Mr. Yusuf Aygun A8003390 Approved Page 2/16 (ELTAS Transformatör Sanayi Ve Ticaret Anonim Şirketi, Izmir TURKEY) (ELTAS Transformatör Sanayi Ve Ticaret Anonim Şirketi, Izmir TURKEY) Identification of the tested object Not requested. Measurement uncertainties The measurement uncertainties of the test results reported in this document are the following: voltage: ±5% current: ±5% time: ±5% temperature: ± 2°C up to 100°C ± 2% above 100°C up to 500°C ± 3%C above 500°C The measurement uncertainties are estimated at the level of twice the standard deviation (corresponding, in the case of normal distribution, to a confidence level about 95 %) and have to be considered as maximum values. Test results The values obtained and the general performance are considered to comply with the reference Standard (see page 1). Laboratory information Test location CESI – Via Rubattino 54 – Milan CESI testing team Mr. Claudio Signorini, Mr. Paolo Sironi Test laboratory P173 Activity code 80246Q Test Report CESI A8003390 Approved Page 3/16 Table of contents 1 LIST OF INSTRUMENTS USED FOR THE TEST ..........................................................................................4 2 TEST ASSEMBLY ................................................................................................................................................4 3 ATMOSPHERIC CONDITIONS.........................................................................................................................4 4 TEST SET UP.........................................................................................................................................................4 5 THERMOCOUPLES POSITIONS ......................................................................................................................4 6 TEST PROCEDURE .............................................................................................................................................5 6.1 6.2 7 CHARACTERISTIC OF THE TESTED OBJECT .........................................................................................................5 TEST EXECUTION ..............................................................................................................................................5 TEST RESULTS ....................................................................................................................................................6 7.1 7.2 7.3 7.4 7.5 7.6 7.7 TEMPERATURE TABLES .....................................................................................................................................6 TEST CHAMBER CALIBRATION RESULTS ............................................................................................................6 TEMPERATURE DIAGRAM ..................................................................................................................................7 TABLE OF RADIANT PANEL ELECTRIC POWER, AIR SPEED, VISIBLE LIGHT TRANSMITTANCE ..............................8 RADIANT PANEL ELECTRIC POWER DIAGRAM ....................................................................................................9 AIR SPEED DIAGRAM .........................................................................................................................................9 VISIBLE LIGHT TRANSMITTANCE DIAGRAM .....................................................................................................10 8 EVALUATION OF THE TEST..........................................................................................................................11 9 TESTED OBJECT PICTURES..........................................................................................................................12 Test Report 1 - 2 CESI A8003390 Approved Page 4/16 LIST OF INSTRUMENTS USED FOR THE TEST Data Acquisition System HP 34970A, equipped with no. 3 board for the Analogic / Digital conversion of voltage and temperature input signal, CESI number 38941; fan tacoanemometer f.s. 10 m/s, minimum resolution 0,25 m/s, CESI number 22009; optical density measuring device, 1,7 m from the test chamber ceiling, CESI number 008235; thermocouples COE-CLERICI type K (full scale 1200 °C) CESI number 14066, 14068, 14069, 14071, 14072, 14035, 14033, 14990, 14992, 38229, 38230, 38231; electronic weighting device area / weighing platform, CESI number 11471, 11789; electronic thermometer TERSID graduated scale from –15 °C to + 50 °C, resolution 0,1 °C, CESI number 13769. TEST ASSEMBLY The tested object was placed over the alcohol container. The distance between the bottom of the alcohol container and the floor of the chamber was 300 mm. The distance between the middle of the windings and the rear wall of the chamber was 600 mm. The distance between the radiant panel and the outer winding surface was 175 mm. The bottom of the radiant panel was 500 mm over the chamber floor. 3 ATMOSPHERIC CONDITIONS External temperature before the test External temperature after the test Temperature of the test chamber / tested object before the test 4 + 10,9 °C + 10,1 °C + 10,9 °C TEST SET UP The test set up comply with the IEC 60076-11 (2004) Standard is identified by CESI as “Plant P173”. It is mainly composed by: • vertical metallic chamber, 4 m high, 1 m wide and 2 m deep, with an air-inlet duct and a cylindrical chimney for the smoke outlet; • radiant panel with 24 resistor of 1 kW each one, buried in white ceramic material; • cylindrical container for the ethylic alcohol with external diameter equal to the MV winding external diameter min. at least 40 mm. 5 THERMOCOUPLES POSITIONS no. 1 – radiant panel, lower side; no. 2 – radiant panel, upper side; no. 3 – air inlet; no. 4 – tested object, front side, about 100 mm from the bottom; no. 5 – tested object, front side, in the middle; no. 6 – tested object, front side, about 100 mm from the top; no. 7 – tested object, in the duct between the windings, about 100 mm from the top; no. 8 – tested object, in the duct between the windings, in the middle; no. 9 – tested object, in the duct between the windings, about 100 mm from the bottom; no. 10 – on the surface of LV windings, at the top; no. 11 – on the surface of MV windings, at the top; no. 12 – at the measuring section of the air outlet. Test Report 6 6.1 CESI A8003390 Approved Page 5/16 TEST PROCEDURE Characteristic of the tested object The dry-type transformer characteristics were: Number of phases Rated voltage of the high-voltage winding (primary winding) Rated frequency Rated power Cooling method Overall dimension 3 10,5 ± 2 x 2,5 % / 0,4 kV 50 Hz 500 kVA AN 0,6 x 0,617 x 0,85 (h) m M.V. external diameter 435 mm L.V. internal diameter 237 mm Total mass 347 kg The alcohol container utilized had the following dimensions: External diameter 535 mm Internal diameter 197 mm Amount of alcohol utilized 6.2 5,82 l Test execution After the installation of the tested object in the test chamber, the test began with the ignition of the alcohol, at the same time the 24 radiant panel resistor were supplied (about 380 V) in order to obtain a thermal flux of about 3 W/cm2 towards the sample, and the forced air purifier were started. The radiant panel, placed about 175 mm far from the front side of the winding, was switched “OFF” 40 minutes later, in the meanwhile the alcohol burnt for approximately 30 minutes. Temperature, electrical power, visible light transmittance and air speed were recorded throughout the test and reported in the following pages. CESI Test Report 7 A8003390 Approved Page 6/16 TEST RESULTS 7.1 Temperature tables Time [min] T.1 [°C] T.2 [°C] T.3 [°C] T.4 [°C] T.5 [°C] T.6 [°C] T.7 [°C] T.8 [°C] T.9 [°C] T.10 [°C] T.11 [°C] T.12 [°C] 0,00 1,50 3,00 4,50 6,00 7,50 9,00 10,50 12,00 13,50 15,00 16,50 18,00 19,50 21,00 22,50 24,00 25,50 27,00 28,50 30,00 31,50 33,00 34,50 36,00 37,50 39,00 40,50 42,00 43,50 45,00 46,50 48,00 49,50 51,00 52,50 54,00 55,50 57,00 60,00 8 161 363 500 593 653 692 716 731 741 748 754 757 761 763 763 763 764 765 763 759 756 756 755 755 756 755 693 551 457 385 331 288 254 226 203 184 168 155 143 11 161 363 505 599 659 699 724 739 747 753 756 755 757 757 756 755 757 760 765 772 778 783 788 792 795 798 739 584 480 400 338 289 249 217 191 170 152 137 125 8 9 11 15 17 20 21 22 23 24 24 24 24 24 24 24 24 24 24 24 24 25 25 25 25 25 25 25 25 26 26 26 26 26 26 26 27 27 27 27 11 67 90 147 179 221 202 269 225 256 253 320 309 309 295 327 367 419 435 315 242 238 238 239 242 244 247 242 211 193 180 171 165 160 153 148 143 139 135 131 11 30 62 106 142 171 193 216 225 247 258 283 288 304 313 316 323 347 360 610 643 624 583 569 567 568 569 561 518 403 324 278 249 228 214 202 192 184 176 169 11 27 74 130 170 197 219 242 262 281 299 318 320 328 330 331 328 680 658 668 639 618 629 679 685 676 664 602 451 356 299 252 225 204 188 177 168 160 154 148 11 174 241 288 325 349 366 380 380 381 388 400 409 421 431 437 456 473 494 523 453 422 404 392 382 515 506 540 542 523 417 364 346 333 323 314 306 299 292 286 10 552 616 678 695 701 679 626 614 597 599 612 625 633 620 614 653 672 694 518 443 403 378 358 343 334 325 316 306 293 279 265 255 245 236 229 221 215 210 205 10 402 511 550 583 632 652 651 666 685 691 692 720 726 737 727 744 748 744 693 570 503 461 428 401 381 361 339 320 299 280 260 249 237 229 221 211 205 201 194 11 82 139 169 197 221 256 266 284 448 447 490 484 494 510 555 545 632 602 657 674 676 659 652 653 640 635 607 510 433 417 285 249 236 220 209 200 190 182 175 10 119 156 177 205 231 245 263 252 345 390 390 432 435 471 523 521 525 488 670 642 628 490 343 333 328 315 307 282 266 251 241 234 230 225 218 211 205 200 196 12 20 33 45 57 68 79 90 102 119 142 164 181 194 206 215 219 220 209 190 169 154 144 136 132 128 126 125 120 113 106 100 94 90 86 82 79 76 74 72 7.2 Test chamber calibration results CESI protocol no.: Average inlet air speed: A8003455 1,94 m/s Test Report 7.3 Temperature diagram CESI A8003390 Approved Page 7/16 CESI Test Report 7.4 A8003390 Approved Table of radiant panel electric power, air speed, visible light transmittance Time [min] EL_POWER [kW] 0,00 1,50 3,00 4,50 6,00 7,50 9,00 10,50 12,00 13,50 15,00 16,50 18,00 19,50 21,00 22,50 24,00 25,50 27,00 28,50 30,00 31,50 33,00 34,50 36,00 37,50 39,00 40,50 42,00 43,50 45,00 46,50 48,00 49,50 51,00 52,50 54,00 55,50 57,00 60,00 0,12 24,42 23,74 24,07 24,05 24,16 24,22 24,13 24,06 24,24 24,20 24,15 24,23 24,35 24,13 24,03 23,86 23,88 23,87 23,89 23,84 23,89 23,89 24,04 23,97 23,94 23,92 0,12 0,11 0,12 0,12 0,12 0,12 0,12 0,12 0,12 0,12 0,12 0,12 0,12 SP2_IEC [m/sec] 0,00 1,36 1,40 1,66 1,77 1,71 1,83 1,93 2,05 2,23 2,19 2,39 2,13 2,43 2,45 2,34 2,37 2,31 2,34 2,19 1,98 1,97 1,91 2,03 1,91 2,02 1,90 1,83 1,82 1,75 1,66 1,70 1,64 1,45 1,61 1,61 1,65 1,60 1,55 1,49 TRANSM [%] 100 99 99 100 99 94 75 49 40 67 88 97 98 99 100 99 99 97 89 77 88 93 95 96 97 96 95 95 97 97 97 95 97 97 98 99 99 99 99 100 Page 8/16 Test Report CESI 7.5 Radiant panel electric power diagram 7.6 Air speed diagram A8003390 Approved Page 9/16 Test Report 7.7 CESI Visible light transmittance diagram A8003390 Approved Page 10/16 CESI Test Report 8 A8003390 Approved Page 11/16 EVALUATION OF THE TEST Weight of the sample before the test Weight of the sample after the test 347 kg 342 kg 220 °C (Text = +24 °C) θ = 196 K θm = 420 K Smoke outlet maximum temperature Smoke outlet maximum temperature-rise Smoke outlet maximum temperature-rise admitted by the standard Smoke outlet temperature after 45 min. Smoke outlet temperature-rise after 45 min Smoke outlet maximum temperature-rise after 45 min. admitted by the standard 106 °C (Text = +26 °C θ = 80 K θm = 140 K Smoke outlet temperature after 60 min. Smoke outlet temperature-rise after 60 min Smoke outlet maximum temperature-rise after 60 min. admitted by the standard 69 °C (Text = +26 °C θ = 43 K θm = 80 K 31,6 % (measured after 12 minutes) 96,03 % 20 % I min. I avg Minimum I avg admitted by the standard Legenda: = minimum visible light transmittance inside the air-oulet chimney I min = arithmetic mean of the visible light transmittance from 20th to 60th minute during the test I avg = external temperature Text NOTE: According to IEC 60076-11 (2004) clause 28.3 document: Τ = X1/P where P = 1 m (lenght of the optical path in the smoke outlet) X = I avg = 0,9603 and consequently T = X = 96,03 % Test results: positive. Test Report 9 CESI TESTED OBJECT PICTURES Photo no. 1 A8003390 Approved Page 12/16 Test Report CESI Photo no. 2 A8003390 Approved Page 13/16 Test Report CESI Photo no. 3 A8003390 Approved Page 14/16 Test Report CESI Photo no. 4 A8003390 Approved Page 15/16 Test Report CESI Photo no. 5 A8003390 Approved Page 16/16
Benzer belgeler
PRODUCT: Ethylene Glycol (MEG) Items Test Method Unit
PRODUCT: Ethylene Glycol (MEG)
MEG is an acronym and may refer to Ethylene glycol (MEG).
Application:
Primarily used as a raw material in the manufacture of polyester fibers and fabric industry, an...