steam trap
Transkript
SDS U2004-40 STEAM TRAP MODEL HR260A ALLOY STEEL SUPERCRITICAL SERVICE THERMODYNAMIC DISC TRAP Features Air-jacketed disc trap for supercritical service in high pressure steam mains and turbines. 1. Inline replaceable valve module for ease of maintenance and low cost of repair. 2. Lapped disc provides steam-tight seal. 3. Air jacket reduces radiant heat loss to reduce no-load cycling and so extend life. 4. Built-in screen with large surface area for extended trouble-free operation. 5. Hardened working surfaces guarantee long service life. 6. Approved by major power plants worldwide for supercritical steam use. Specifications Model HR260A Connection Pressure-Temperature Rating** Socket Welded Butt Welded DN 15, 25 Size 260 PMO 400 16 Minimum Operating Pressure (barg) Maximum Operating Temperature (˚C) TMO 550 Maximum Allowable Pressure (barg) PMA* 260 @ 550 ˚C Maximum Allowable Temperature (˚C) TMA* TMA (˚C) Maximum Operating Pressure (barg) 550 500 550 @ 260 barg 1 bar = 0.1 MPa * PRESSURE SHELL DESIGN CONDITIONS (NOT OPERATING CONDITIONS) ** This Rating Graph is based on Allowable Stress Values of ASTM-Materials at each temperature. CAUTION No. 200 100 50% of Inlet Pressure Maximum Back Pressure 300 0 0 50 100 150 200 PMA (barg) 250 300 To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range. Local regulations may restrict the use of this product to below the conditions quoted. Description DIN* Material Alloy Steel A182 F22 Cl.3 1.7380 Alloy Steel (9%Cr - 1%Mo)** 1.4903 ASTM/AISI* ― 1 ⃝ Body 2R ⃝ 3R ⃝ 4R ⃝ 5 ⃝ 6 ⃝ 7 MR ⃝ 8 MR ⃝ 9R ⃝ 10 ⃝ 11 ⃝ 12 ⃝ 13 R ⃝ 14 ⃝ 15 ⃝ Cover Stainless Steel SUS420J2 1.4031 AISI420 Module Valve Seat Stainless Steel SUS440C 1.4125 AISI440C 12 Disc Stainless Steel SUS440C 1.4125 AISI440C 11 Eye Nut Carbon Steel SS400 1.0037 A6 10 Spacer Carbon Steel SS400 1.0037 A6 Graphite/Stainl. Stl. SUS309S+Cb Graphite/Stainl. Stl. SUS309S+Cb 2 Module Gasket - /1.4833 - /AISI309S+Cb - /1.4833 7 - /AISI309S+Cb 9 Module Gasket Screen inside/outside Stainless Steel SUS430/304 ― Body Bolt Alloy Steel SNB16 1.4016/4301 AISI430/304 1.7711 A193 Gr.B16 Cover Nut Alloy Steel SNB7 1.7225 A193 Gr.B7 Cap Carbon Steel SPCC 1.0330 A109 Guide Pin Stainless Steel SUS304 1.4301 AISI304 Nameplate*** Stainless Steel SUS304 1.4301 AISI304 Hexagon Nut Carbon Steel SS400 1.0037 A6 * Equivalent materials ** Option *** Not shown Replacement kits available: (M) maintenance parts, (R) repair parts 5 15 6 4 3 8 13 1 Copyright C Consulting & Engineering Service Dimensions • HR260A HR260A Socket Welded* L Socket Welded DN H1 15 H 25 (mm) L H H1 φD 160 208 179 53.5 h Weight (kg) 14 18 φC 21.8 33.9 D C * ASME B16.11-2005, other standards available h • HR260A HR260A Butt Welded* L Butt Welded DN H1 15 H 25 L H H1 165 208 179 (mm) φD φD1 φd 28 22 16 40 35 27 h Weight (kg) 20 18 * DIN 3239 Form C (PN250), other standards available D D1 d 30˚ h Discharge Capacity Discharge Capacity (kg/h) 250 200 180 160 140 120 100 16 20 30 40 50 60 70 80 90 100 Differential Pressure (bar) 150 200 225 260 1 bar = 0.1 MPa 1. Differential pressure is the difference between the inlet and outlet pressure of the trap. 2. Recommended safety factor: at least 2. Copyright (M) C SDS U2004-40 Rev. 6/2014 Products for intended use only. Specifications subject to change without notice.
Benzer belgeler
free float® steam trap
2. Differential pressure is the difference
between the inlet and outlet pressure
of the trap.
3. Capacities are based on continuous
discharge of condensate 6 °C below
saturated steam temperature.
4...
steam trap
5. Built-in screen for trouble-free service.
6. High grade reusable gaskets.
7. Hardened working surfaces for long life.
free float® steam trap
2. Differential pressure is the difference between the inlet and outlet pressure of the trap.
3. Capacities are based on continuous discharge of condensate 6 °C below saturated steam temperature.
process float steam trap
* JL14-X has a screwed-in flange ** Optional JLH14-B with bimetal-type air vent unit for initial air venting
PRESSURE SHELL DESIGN CONDITIONS (NOT OPERATING CONDITIONS):
Maximum Allowable Pressure ...
Specifications
cleaning and reduces maintenance costs.
5. High-quality stainless steel internals and
hardened valve surfaces ensure reliability.
elastomer sitli sürgülü vana (pn 25, f4)
Sıcak ve soğuk su sistemleri, asit ve alkali özelliği bulunmayan sıvı akışkanlar
Hot and cold water systems, non-acidic and non-flammable liquid fluids